Klebs & Hartmann drawing set A.-Nr. 11092 0002 / Z.-Nr. 6950 09 · Anlage 4.746.164 · Drawings rev b Mai 2010 · merged with site record «IO list ACW.xlsx» (rev 6)
Cross-references:/42.6 = Blatt 42, column 6. Locations: +CP01 power field, +CP02 control field, +CP03 instrumentation field, =LP01 local panel, =Turbine, =Generator, K02 gen. CB panel, =Kondensator, +JB100 bearing temps. PDF page ≠ Blatt — see Sheet index.
I/O map — drawings merged with site symbol table (IO list ACW.xlsx rev 6)
Address
Symbol
Description
Loop dwg (Blatt)
Source
Notes
Addresses in STEP7 IEC notation (I/Q/PIW = E/A/PEW on the German drawings). Source both = drawing and site agree; site = from site I/O list only (sheet not yet deep-extracted). Amber rows carry a conflict/verification note — see the Conflicts tab. M-addresses are program markers.
SC900 governor (-45A2) — terminal / function map (site record)
SC900 terminal
Function
Alarm / trip limit values (site record)
Description
Limit
Unit
The site file also contains an SC900_Future tab — a planned migration of SC900 governor I/O onto PLC cards (incl. a 1794-IE12 analog card). That is a future concept, not as-built, and is excluded from the as-built tables.
Conflicts: drawings (rev b, Mai 2010) vs site record (IO list rev 6)
Item
Drawing says
Site record says
Assessment
Circuit sheet summaries (extracted so far)
Each sheet includes a signal-flow diagram — read left to right: — dashed boxes are rails / cross-sheet signals.